There are three main types of PEMS, and each suits different situations. A Predictive Emissions Monitoring System (PEMS) calculates emissions such as NOx, CO, CO2 and SO2 from process data. It does not need physical analyzers.
The US EPA has accepted PEMS since the early 1990s. Today, hundreds of sites around the world use it. However, not every PEMS works the same way. This guide explains how each type works and how to choose.
A Quick Primer: CEMS and PEMS
Boilers, heaters, reformers and gas turbines produce pollutants. Regulators require many facilities to monitor these emissions continuously. There are two ways to do this:
- CEMS: hardware that measures stack gases with physical analyzers.
- PEMS: software that predicts emissions from a model and live process data.
1. First Principle Models
First principle PEMS use equations based on how emissions actually form. Emissions fall into two groups:
- Stoichiometric emissions depend mainly on fuel composition. Examples include SO2 and CO2.
- Rate-formation emissions depend on combustion conditions such as temperature and pressure. Examples include NOx and CO.
Strengths: the model reflects real combustion physics. It also tends to need fewer test measurements.
Limitations: each model must fit one specific source and its inputs. Building or updating it takes deep combustion expertise, usually from the vendor.
2. Neural Network Models
Neural network PEMS learn the link between inputs and emissions from historical data. The data passes through layers of connected nodes.
Strengths: they need little prior process knowledge. They can also capture complex behavior.
Limitations: training must cover the full operating range, including different loads, fuels and weather. Outside that range, accuracy can drop. These models can also be hard to inspect or update without the vendor.
3. Statistical (Hybrid) Models
Statistical PEMS use methods such as regression to link process inputs with emissions. During development, the unit runs across its operating range. Meanwhile, the team logs process data and reference emissions. The model then fits that data.
Strengths: the model needs no detailed combustion chemistry. With training, site staff can often update it themselves.
Limitations: development needs good statistical skills. The model also works best within its training range.
Certification and Ongoing Accuracy
Whatever the model, all types of PEMS must pass reference-method testing. In the US, EPA Performance Specification 16 sets the rules for PEMS certification. In addition, 40 CFR Part 60 and Part 75 cover testing, accuracy and audits.
Which Types of PEMS Suit Which Sites?
- If fuel or feed varies widely, as in an incinerator, a hardware CEMS usually works better.
- With steady fuel, such as natural gas or fuel oil, all three types of PEMS can meet the rules.
- Neural network PEMS often cost more, but they can deliver high accuracy in complex operations.
- First principle and statistical models tend to have similar accuracy and cost.
- If your team wants to maintain the model, a statistical model is often the most practical choice.
- If you prefer the vendor to maintain it, consider a first principle or neural network model.
See also: CEMS vs PEMS and our PEMS consulting services.
Need Help Choosing a PEMS?
Discuss your project or call (703) 652-1845